| POWER |
INPUT |
OUTPUT |
FREQUENCY |
STANDARDS |
| FROM
4000 TO 25000VA |
230V
|
230V
|
50/60
Hz |
EN
61558-2-4 |
| IEC
742 |
|
from 110 to 550V
|
from 24 to 550V
|
CEI
96-2 |
| BS
3535 |
Open type
Protection IP00
Isolation class H (At max 45°C)
Separate copper windings cl. H
Resing impregnated and tropicalised
Earthed copper screen between primary and secondary
Connections on terminal blocks up to 10kVA (or to 63A)
connections on brass bolts up to 12,5kVA (or from 64A)
Optional: mounted in metal enclosure RAL7032, IP23
|


|
 |
| power |
part
no. |
losses |
short
circ. |
regulation |
dimensions
mm. |
DWG |
weight |
box |
| VA |
W |
voltage
% |
% |
A |
B |
C |
D |
E |
F |
kg. |
code |
| 3150 |
TMIC03 |
130 |
3.5 |
3.0 |
240 |
230 |
320 |
200 |
125 |
12 |
A |
34.0 |
SA02 |
| 4000 |
TMIC04 |
145 |
2.9 |
2.6 |
240 |
240 |
320 |
200 |
135 |
12 |
A |
38.0 |
SA02 |
| 5000 |
TMIC05 |
180 |
2.7 |
2.6 |
240 |
250 |
320 |
200 |
145 |
12 |
A |
44.0 |
SA02 |
| 6300 |
TMIC06 |
200 |
2.7 |
2.6 |
280 |
230 |
400 |
220 |
145 |
12 |
A |
49.0 |
SA03 |
| 8000 |
TMIC08 |
210 |
2.7 |
2.6 |
280 |
240 |
400 |
220 |
155 |
12 |
A |
60.0 |
SA03 |
| 10000 |
TMIC10 |
280 |
2.5 |
2.3 |
280 |
250 |
400 |
220 |
165 |
12 |
A |
65.0 |
SA03 |
| 15000 |
TMIC15 |
400 |
2.5 |
2.2 |
320 |
260 |
450 |
260 |
185 |
12 |
B |
92.0 |
SA04 |
| 20000 |
TMIC20 |
600 |
2.4 |
2.0 |
320 |
280 |
450 |
260 |
205 |
12 |
B |
116.0 |
SA04 |
| 25000 |
TMIC25 |
700 |
2.1 |
2.0 |
320 |
280 |
450 |
260 |
205 |
12 |
B |
131.0 |
SA04 |
| ASK
FOR CODES AND SPECIFICATION OF HIGHER RATINGS |
|
 |
 |
|
A |
B |
|
PART NO
SHOWN ABOVE REPRESENT THE STANDARD IN.230V-OUT.230V TYPE. IF
DIFFERENT INPUT-OUTPUT VLTAGES ARE REQUIRED, THERE MUST BE
SPECIFIED IN THE DESCRIPTION OF YOUR ORDER. |
|
FOR
SECONDARY VOLTAGE BELOW 50V A.C., TMIC TRANSFORMERS ARE
MANUFACTURED ACCORDING THE EN61558-2-6 STANDARDS FOR SAFETY
ISOLATION TRANSFORMERS |
 |
|
UL
CERTIFIED VERSION AVAILABLE
RECOGNIZED COMPONENT (USA)
CONTACT US FOR YOUR ENQUIRIES |
 |
|